APPENDICES
A
Appendix
2 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
(8) Module monitor/control area (address: 8000
H
to 80FF
H
)
Do not read/write data from/to use prohibited remote buffer memory areas.
Doing so does not guarantee the functions of the bridge module.
(a) Module monitor/control area (address: 8000
H
and 8080
H
)
The status of Module monitor area (address: 8000
H
) is transferred to Bridge module operating status (RWr0) of
the remote register.
The status of Module control area (address: 8080
H
) is transferred to Bridge module setting (RWw0) of the
remote register.
• Details of remote registers (
Page 103, Appendix 1)
Do not read/write data from/to use prohibited remote buffer memory areas.
Doing so does not guarantee the functions of the bridge module.
Communication
direction
Address
Description
Default value
Bridge module to
master station
8000
H
Module monitor area (read)
0100
H
8001
H
Error code
0000
H
8002
H
Warning code
0000
H
8003
H
Use prohibited
807F
H
Master station to
bridge module
8080
H
Module control area (write)
8081
H
Use prohibited
80FF
H
Module monitor area (read) (address: 8000
H
)
Module control area (write) (address: 8080
H
)
b0 to b9
Use prohibited
b0 to b9
Use prohibited
b10
Error status flag
b10
Error clear request flag
b11
Remote READY
b11 to b15
Use prohibited
b12
Warning status flag
b13 to b15
Use prohibited
Содержание NZ2GF-CCB
Страница 1: ...CC Link IE Field Network CC Link Bridge Module User s Manual NZ2GF CCB ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 35: ...33 CHAPTER 4 THE PROCEDURE BEFORE OPERATION 4 Memo ...
Страница 143: ...141 APPENDICES A Appendix 7 External Dimensions Appendix 7 External Dimensions 160 65 4 5 68 9 2 Unit mm ...
Страница 145: ...I 4 4 7 8 143 Memo ...
Страница 149: ......