47
MUZ-GC60NA
-
C2
MUZ-GC71NA
N Check of HPS
1. Disconnect the connector CN681 in the outdoor electronic control P.C. board.
2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.
Check the resistance between each terminal.
Is HPS protection displayed immediately after
compressor starts?
Replace HPS.
Replace the outdoor electronic
control P.C. board.
Normal
In
fi
nity
No
0
Ω
Yes
Reconnect CN681.
Turn ON power supply to the indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.