35
MUZ-GC50NA MUZ-GC60NA MUZ-GC71NA
Part name
Check method and criterion
Figure
Defrost thermistor (RT61)
Ambient temperature ther-
mistor (RT65)
Outdoor heat exchanger tem-
perature thermistor
(RT68)
Measure the resistance with a tester.
Refer to 9-6. "Test point diagram and voltage", 1. "Inverter P.C.
board" or 2. "Outdoor electronic control P.C. board”, the chart of
thermistor.
Discharge temperature
thermistor
(RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 9-6. "Test point diagram and voltage", 1. "Inverter P.C.
board" or 2. "Outdoor electronic control P.C. board", the chart of
thermistor.
Fin temperature
thermistor (RT64)
Compressor (MC)
Measure the resistance between terminals using a tester.
(Winding temperature : -10 ~ 40°C)
Normal
GC50/60NA-
C1
GC50/60NA-
C2
GC71
0.40 ~ 0.49
Ω
0.86 ~ 1.06
Ω
1.29 ~ 1.49
Ω
Outdoor fan motor (MF)
Measure the resistance between lead wires using a tester.
(Part temperature : -10 ~ 40°C)
Color of lead wire
Normal
RED – BLK
13.4 ~ 16.4
Ω
BLK – WHT
WHT – RED
R. V. coil
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Normal
GC50NA-
C2
GC60NA-
C2
Other models
1.32 ~ 1.62 k
Ω
2.6 ~ 3.3 k
Ω
Linear expansion valve
Measure the resistance using a tester.
(Part temperature : -10 ~ 40°C)
Color of lead wire
Normal
WHT – RED
37.4 ~ 53.9
Ω
RED – ORN
YLW – BRN
BRN – BLU
High pressure switch
(HPS)
GC60NA
-
C2
GC71NA
Pressure (MPa)
Normal
3.7 ± 0.15
Close
4.8
+0.05
-0.1
Open
W
U
V
WHT
RED
BLK
LEV
WHT
RED
YLW BRN
ORN
BLU
U
RED
WHT
BLK
V
W
(W)
(V)
(U)