I Check of outdoor fan motor
Is the resistance between each ter-
minal of outdoor fan motor normal?
(Refer to 9-4.)
Check the connection between the
connector CN931 and CN932.
Disconnect CN932 from outdoor electronic control P.C. board
and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
MUZ-GC50/60/71NA
Replace the outdoor electronic control P.C. board.
Check the resistance of fan motor. (Refer to
9-4.)
Is the resistance of
fan motor normal?
Replace the outdoor
fan motor.
Disconnect the connector CN771 on the
power P.C. board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION
INDICATOR lamp on
the indoor unit light up?
After 3 minutes, is
there voltage 220 -
230 VAC between
CN771 and on
the power P.C. board?
Replace the outdoor
fan motor.
Replace the
power P.C. board.
Yes
No
Yes
No
MUZ-GC25/35NA