28
MUZ-GC50NA-
C1
MUZ-GC60/71NA
The left lamp of
OPERATION
INDICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
Condition Correspondence
Indoor/outdoor
unit failure
mode recall
function
LED 1
LED 2
OFF None
(Normal)
—
—
—
—
—
2-time
fl
ash
Outdoor power system
Lighting Lighting Overcurrent protection stop is continuously
performed 3 times within 1 minute after the
compressor gets started, or when converter
protection stop or bus-bar voltage protection
stop is continuously performed 3 times within 3
minutes after start-up.
• Check the connection of the
compressor connecting wire.
• Refer to 9-5. "How to check
inverter/compressor".
• Check the stop valve.
○
3-time
fl
ash
Discharge temperature
thermistor
Lighting Once
Thermistor shorts or opens during compressor
running.
• Refer to 9-5. "Check of
outdoor thermistors".
○
Defrost thermistor
Lighting Once
Ambient temperature
thermistor
Lighting Twice
Fin temperature thermistor
Lighting 3 times
P.C. board temperature
thermistor
Lighting 4 times
• Replace the outdoor
electronic control P.C. board.
Outdoor heat exchanger
temperature thermistor
Lighting 9 times
• Refer to 9-5. "Check of
outdoor thermistors".
4-time
fl
ash
Over current
Once
Goes out 28 A current
fl
ows into intelligent power module. • Reconnect compressor
connector.
• Refer to 9-5. "How to check
inverter/compressor."
• Check the stop valve.
—
5-time
fl
ash
Discharge temperature
Lighting Lighting Discharge temperature exceeds 116°C during
operation. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3
minutes later.
• Check refrigerant circuit and
refrigerant amount. • Refer
to 9-5. "Check of LEV".
—
6-time
fl
ash
High pressure
Lighting Lighting High-pressure is detected with the high-pressure
switch (HPS) during operation.
•Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
—
The outdoor heat exchanger temperature
exceeds 70°C during cooling or the indoor gas
pipe temperature exceeds 70°C during heating.
7-time
fl
ash
Fin temperature
3 times
Goes out The
fi
n temperature exceeds 87°C during
operation.
• Check around outdoor unit.
• Check outdoor unit air
passage.
• Refer to 9-5. "Check of
outdoor fan motor".
—
P.C. board temperature
4 times
Goes out The P.C. board temperature exceeds 70°C
during operation.
8-time
fl
ash
Outdoor fan motor
Lighting Lighting Failure occurs continuously 3 times within 30
seconds after the fan gets started.
• Refer to 9-5. "Check of
outdoor fan motor".
—
9-time
fl
ash
Nonvolatile memory data
Lighting 5 times
Nonvolatile memory data cannot be read
properly.
• Replace the outdoor
electronic control P.C. board.
○
10-time
fl
ash Discharge temperature
Lighting Lighting The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 9-5. "Check of
LEV".
—
11-time
fl
ash Communication error between
P.C. boards
Lighting 6 times
Communication error occurs between the
electronic control P.C. board and power board
for more than 10 seconds.
• Check the connecting wire
between outdoor electronic
control P.C. board and power
board.
—
The communication between boards protection
stop is continuously performed twice.
○
Current sensor
Lighting 7 times
A short or open circuit is detected in the current
sensor during compressor operating.
• Replace the power board.
—
Current sensor protection stop is continuously
performed twice.
○
Zero cross detecting circuit
5 times
Goes out Zero cross signal cannot be detected while the
compressor is operating.
• Check the connecting wire
among electronic control P.C.
board, noise
fi
lter P.C. board
and power board.
—
The protection stop of the zero cross detecting
circuit is continuously performed 10 times.
○
Converter
5 times
Goes out A failure is detected in the operation of the
converter during operation.
• Replace the power board.
—
Bus-bar voltage (1)
5 times
Goes out The bus-bar voltage exceeds 400 V or falls to
200 V or below during compressor operating.
Bus-bar voltage (2)
Even if this protection stop
is performed continuously 3
times, it does not mean the
abnormality in outdoor power
system.
6 times
Goes out The bus-bar voltage exceeds 400 V or falls to 50
V or below during compressor operating.
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-3.).