39
MUZ-GC25/35NA MUZ-GC50NA-
C2
Thermistor
Symbol
Connector, Pin No.
Board
Defrost
RT61
Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature
RT62
Between CN641 pin3 and pin4
Fin temperature
RT64
Between CN642 pin1 and pin2
Ambient temperature (
GC50
)
RT65
Between CN643 pin1 and pin2
Outdoor heat exchanger temperature (
GC50
)
RT68
Between CN644 pin1 and pin3
MUZ-GC50NA-
C1
MUZ-GC60/71NA
Thermistor
Symbol
Connector, Pin No.
Board
Defrost
RT61 Between CN661 pin 1 and pin 2
Outdoor electronic control P.C.
board
Discharge temperature
RT62 Between CN661 pin 3 and pin 4
Outdoor heat exchanger temperature
RT68 Between CN661 pin 7 and pin 8
Ambient temperature
RT65 Between CN663 pin 1 and pin 2
Fin temperature
RT64 Between CN3 pin 1 and pin 2
Outdoor power board
G Check of outdoor thermistors
Replace the thermistor except RT64.
When RT64 is abnormal, replace the inverter P.C.
board or the outdoor power board.
Replace the inverter P.C. board or the
outdoor electronic control P.C. board.
No
No
Is the thermistor normal? (Refer to 9-6.1.
or 9-6.2.)
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more
without showing thermistor abnormality?
OK.
(Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 9-4.
In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
No
Replace the inverter
P.C. board.
Is there 220 - 230 VAC between CN721
and on the inverter P.C. board 3
minutes after the power supply is turned
ON?
Yes
Replace the 4-way valve.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Yes
Replace the inverter
P.C. board.
Is there 220 - 230 VAC between CN721
and on the inverter P.C. board 3
minutes after the power supply is turned
ON?
No
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61)
between the compressor and the
intelligent power module.
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
MUZ-GC25/35NA MUZ-GC50NA-
C2