Power supply
Connection
MELSERVO J2-Super
3 - 19
Timing chart
Emergency stop
For safety’s sake an EMERGENCY OFF switch must always be installed between the terminals
EM1 and SG. When the contact is interrupted, the servo motor is switched to a resistance brake
(dynamic brake) integrated into the unit and brought to a stop as soon as possible.
Simultaneously the EMERGENCY OFF message (E6) appears on the display.
During ordinary operation, do not use emergency stop circuit to alternate stop and run.
S000979C
Fig. 3-19:
Timing chart for switching on the power supply
S000980C
Fig. 3-20:
Emergency stop circuit
(3s )
60m s
60m s
10m s
Main circuit and
control circuit
Base circuit
Servo ON command
(from controller)
ON
OFF
ON
OFF
ON
OFF
"Servo ON" command accepted
VDD
COM
EM1
SG
Servo amplifier
Emergency stop