General description
Absolute position detection system
MELSERVO J2-Super
6 - 1
6
Absolute position detection system
6.1 General
description
6.1.1 Specifications
Time to hold data by a battery with power off.
Period during which data can be held by the super capacitor in the encoder after power-off,
with the battery voltage low or the battery removed, or during which data can be held with
the encoder cable disconnected. Battery replacement should be finished within this period.
b
CAUTION:
If an absolute position erase alarm (25) has occurred, always perform home position
setting again. Not doing so can cause runaway.
Item
Description
System
Electronic battery backup system
Battery
Lithium battery A6BAT or MR-BAT
Maximum revolution range
Reference position
±
32767 rev.
Maximum speed at power failure
500r/min
Battery backup time
Approx. 10000h
Data holding time during battery replacement
2h at delivery, 1h in 5 years after delivery
Battery storage period
Approx. 5 years
Tab. 6-1:
Specification overview
Содержание MELSERVO MRJ2S-B
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 14: ...VIII ...
Страница 18: ...Contents XII ...
Страница 48: ...Introduction System configuration 1 30 ...
Страница 58: ...Installation General environmental conditions 2 10 ...
Страница 86: ...Connection Station number setting 3 28 ...
Страница 122: ...Operation Gain 4 36 ...
Страница 134: ...Absolute position detection system General description 6 6 ...
Страница 146: ...Accessories Special accessories 7 12 ...
Страница 148: ...Maintenance and Inspection Life 8 2 ...
Страница 174: ...Specifications Standard specifications 10 16 ...
Страница 176: ...EMC Directives Requirements 11 2 ...
Страница 198: ...Index iv ...
Страница 199: ......