Operation
Parameter
4 - 18
Number
Symbol
Initial value
Unit
Setting range
19
FFC
0
%
0–100
Feed forward gain
Pre-regulation to minimise the control deviation for position control.
When the setting is 100%, the droop pulses during operation at constant speed are nearly zero. However, sudden
acceleration/deceleration will increase the overshoot.
20
INP
100
Pulse
0–50000
In-position range
Used to set the droop pulse range in which the in-position will be output to the controller.
The control deviation is not affected by the electronic gear. Make setting in the feedback pulse unit
(parameter No. 6).
Example:
when you want to set 10
µ
m in the conditions that the ballscrew is direct coupled, the lead is 10mm, and the
feedback pulses are 8192 pulses/rev (parameter No. 6: 1), set "8" in parameter 20 as indicated by the following
expression.
21
MBR
100
ms
0–1000
Electromagnetic brake sequence output
Used to set a time delay from when the electromagnetic brake interlock signal (MBR) turns off until the base circuit
is shut off.
22
MOD
0100
Refer description
Analog monitor output
MO1
The settings corresponds to MO2
MO2
Setting
Servo amplifier 200V
Servo amplifier 400V
0
Servo motor speed (±8V/max. speed)
1
Torque (±8V/maxi. torque)
2
Servo motor speed (+8V/max. speed)
3
Torque (+8V/maxi. torque)
4
Current set point
(±8V/max. rated current)
5
Speed set point
(±8V/max. speed)
6
Contouring error
(±10V/128 Pulse)
7
Contouring error (±10V/2048 Pulse)
8
Contouring error (±10V/8192 Pulse)
9
Contouring error (±10V/32768 Pulse)
A
Contouring error (±10V/131072 Pulse)
B
Bus voltage (+8V/400V)
Bus voltage (+8V/800V)
23
OP1
0000
Refer description
Function selection 1: Used to make the servo forced stop function invalid
Tab. 4-13:
Parameter list details (5)
10
10
6
–
×
10
10
3
–
×
------------------------
81920
×
8.192
8
=
=
0
0
0
0
0
Servo forced stop selection
0: Valid (Use the forced stop EM1.)
1: Invalid (Do not use the forced stop EM1. Automatically switched on internally.)
Содержание MELSERVO MRJ2S-B
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 14: ...VIII ...
Страница 18: ...Contents XII ...
Страница 48: ...Introduction System configuration 1 30 ...
Страница 58: ...Installation General environmental conditions 2 10 ...
Страница 86: ...Connection Station number setting 3 28 ...
Страница 122: ...Operation Gain 4 36 ...
Страница 134: ...Absolute position detection system General description 6 6 ...
Страница 146: ...Accessories Special accessories 7 12 ...
Страница 148: ...Maintenance and Inspection Life 8 2 ...
Страница 174: ...Specifications Standard specifications 10 16 ...
Страница 176: ...EMC Directives Requirements 11 2 ...
Страница 198: ...Index iv ...
Страница 199: ......