8 Application Steps
8.1 Optimize Image
45
8
Test
This function can actually test for reading codes by using created settings.
Additionally, the number of trigger input can be set by using "Trigger On" and "Trigger Off" in the drop-down window of the
[Test] button.
Note: The image transmission may be disabled when codes are read at high-speed because the speed may be limited by
reading settings, codes to be read, or a connection interface.
Trigger On
Trigger Off
Trigger occurrence frequency
20 ms
1980 ms
0.5 times (0.5 Hz) per second
20 ms
980 ms
1 time (1 Hz) per second
20 ms
480 ms
2 times (1 Hz) per second
20 ms
180 ms
5 times (1 Hz) per second
20 ms
80 ms
10 times (1 Hz) per second