Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FN
C
275-
FN
C
279
Da
ta
Transf
er 3
32
FN
C
280-
FN
C
289
H
igh Speed
Pr
ocessing 2
33
FN
C
29
0-F
N
C
299
Ext
ens
ion Fi
le
R
egi
ster
34
FN
C
300-
FN
C
305
FX
3U
-C
F-A
D
P
35
SFC•S
TL
Pr
ogr
am
m
ing
36
In
ter
rupt
Functi
on
37
Special D
evice
38
E
rro
r C
ode
A
Ve
rs
ion U
p
In
fo
rm
atio
n
B
Execution T
im
es
Circuit error [M8066(D8066)]
0000
⎯
No error
6610
Stops
operation
LD, LDI is continuously used 9 times or more.
This error occurs when a combination of
instructions is incorrect in the entire circuit block or
when the relationship between a pair of instructions
is incorrect.
Modify the instructions in the program mode so that
their mutual relationship becomes correct.
6611
More ANB/ORB instructions than LD/LDI
instructions
6612
Less ANB/ORB instructions than LD/LDI
instructions
6613
MPS is continuously used 12 times or more.
6614
No MPS instruction
6615
No MPP instruction
6616
No coil between MPS, MRD and MPP, or incorrect
combination
6617
Instruction below is not connected to bus line:
STL, RET, MCR, P, I, DI, EI, FOR, NEXT, SRET,
IRET, FEND or END
6618
STL, MC or MCR can be used only in main
program, but it is used elsewhere (e.g. in interrupt
routine or subroutine).
6619
Invalid instruction is used in FOR-NEXT loop:
STL, RET, MC, MCR, I (interrupt pointer) or IRET.
6620
FOR-NEXT instruction nesting level exceeded
6621
Numbers of FOR and NEXT instructions do not
match.
6622
No NEXT instruction
6623
No MC instruction
6624
No MCR instruction
6625
STL instruction is continuously used 9 times or
more.
6626
Invalid instruction is programmed within STL-RET
loop:
MC, MCR, I (interrupt pointer), SRET or IRET.
6627
No STL instruction
6628
Invalid instruction is used in main program:
I (interrupt pointer), SRET or IRET
6629
No P or I (interrupt pointer)
6630
No SRET or IRET instruction
STL-RET / MC-MCR instructions programmed in
the subroutine.
6631
SRET programmed in invalid location
6632
FEND programmed in invalid location
Error
code
PLC operation at
error occurrence
Contents of error
Action