![Mitsubishi Electric MELSEC FX3G Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/mitsubishi-electric/melsec-fx3g/melsec-fx3g_programming-manual_239083041.webp)
39
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
2 Overview (Sequence Program)
2.6 Program Memory and Devices
1
Int
roduct
ion
2
O
ver
view
3
In
str
uc
tion
Li
st
4
D
evices
in D
etail
5
Spec
ified t
he
D
evice &
C
onst
ant
6
Bef
ore
Pr
ogr
am
m
ing
7
B
asic
In
st
ru
ct
io
n
8
FN
C
00-FN
C
09
P
rogr
am
F
low
9
FN
C
10
-FN
C
19
Mo
ve
&
Co
mp
are
10
FNC2
0-F
NC2
9
Ar
ith.
&
Logic
O
per
ation
b) FX
3G
PLCs
*1.
These registers can be changed from the general type to the latched (battery backed) type by the
parameter setting when the optional battery is installed.
*2.
Some devices are cleared when the PLC status switches from STOP to RUN.
→
For special data registers, refer to Chapter 37.
Item
Power OFF
Power
OFF
→
ON
STOP
→
RUN
RUN
→
STOP
Contact image
memory
(X, Y, M, S)
Input relay (X)
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
Output relay (Y)
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
General type auxiliary relay
(M)
Cleared.
*1
Does not
change.
Cleared.
Does not change while M8033
is ON.
latched (battery backed) type
auxiliary relay (M)
Does not change.
Special type auxiliary
relay (M)
Cleared.
Set to initial
values.
*2
Does not change.
*2
General type state relay (S)
Cleared.
*1
Does not change.
latched (battery backed) type
state relay (S)
Does not change.
Annunciator (S)
Does not change.
Timer contact
Time counting coil
(T)
For 100 ms
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
For 10 ms
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
For 1 ms
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
Retentive type for
100 ms
Does not change.
Retentive type for 1 ms
Does not change.
Counter contact
Counting coil
Reset coil (C)
General type
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
latched (battery backed) type
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.
High speed type
Cleared.
Does not
change.
Cleared.
Does not change while M8033
is ON.