Programming Manual - Basic & Applied Instruction Edition
9 Move and Compare – FNC 10 to FNC 19
9.3 FNC 12 – MOV / Move
1
Int
roduct
ion
2
O
ver
view
3
In
str
uc
tion
Li
st
4
D
evices
in D
etail
5
Spec
ified t
he
D
evice &
C
onst
ant
6
Bef
ore
Pr
ogr
am
m
ing
7
B
asic
In
st
ru
ct
io
n
8
FN
C
00-FN
C
09
P
rogr
am
F
low
9
FN
C
10
-FN
C
19
Mo
ve
&
Co
mp
are
10
FNC2
0-F
NC2
9
Ar
ith.
&
Logic
O
per
ation
Program examples
1. When reading the current value of a timer and counter
2. When indirectly specifying the set value of a timer or counter
As the set value of the timer T20, two values can be specified by turning ON or OFF the switch X002.
For specifying more than two set values, more than one switch is required.
3. When transferring a bit device
The program written by basic instructions shown on the right can be expressed using MOV instruction as
shown below.
4. When transferring 32-bit data
Make sure to use DMOV instruction for transferring the operation result of an applied instruction (such as
MUL) whose operation result is output in 32 bits, and for transferring a 32-bit numeric value or transferring the
current value of a high speed counter (C235 to C255) which is a 32-bit device.
X001
FNC 12
MOV
T 0
D 20
(Current value of T0)
→
(D20)
The operation is the same as a counter.
X002
FNC 12
MOV
K100
D 10
M 0
T 20
(K100)
→
(D 10)
When X002 is ON, D10 = K100 (10-second timer).
When X002 is OFF, D10 = K50 (5-second timer).
D 10
X002
FNC 12
MOV
K 50
D 10
(K50)
→
(D 10)
X000
X001
X002
X003
Y000
Y001
Y002
Y003
FNC 12
MOV
K1X000 K1Y000
M8000
RUN monitor
FNC 12
DMOV
C235 D20(D21)
FNC 12
DMOV
D0(D1) D10(D11)
(D 1,D 0)
→
(D 11,D 10)
(Current value of C235)
→
(D21, D20)
Command
input
Command
input