Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
16 External FX Device – FNC 80 to FNC 89
16.6 FNC 85 - VRRD / Volume Read
11
FNC3
0-F
NC3
9
R
otati
on and
Shif
t
12
FNC4
0-F
NC4
9
D
ata
O
per
ati
on
13
FN
C
50-FN
C
59
H
igh Speed
Pr
ocess
ing
14
FM
C
60-
FN
C
69
H
andy
In
st
ru
ct
ion
15
FNC7
0-F
N
C7
9
Ex
ter
nal
FX
I/O
D
evice
16
FN
C
80-FN
C
89
Ext
ernal FX
De
vic
e
17
FN
C
100-
FN
C
109
Da
ta
Transf
er 2
18
FN
C
110-
FN
C
139
Fl
oati
ng Poi
nt
19
FN
C
140
-F
N
C
14
9
Da
ta
O
per
ati
on 2
20
FN
C
150-
FN
C
159
Posit
ioning
C
ontr
ol
2. Example in which the analog values of the variable analog potentiometers Nos. 0 to 7 are
read in turn, and used as analog timers
K0 to K7 are specified in
of the VRRD instruction in accordance with the values of the variable
potentiometers VR0 to VR7.
Index (Z = 0 to 7) is used for indexing in the sequence below, and K0Z indicates K0 to K7.
Cautions
• In 14-point and 24-point type FX
3G
PLCs, the variable analog potentiometer board can be connected to the
option connector 1, and occupies the communication channel ch1.
In this case, the communication function using the communication channel ch1 is not available when the
VRRD or VRSC instruction is used.
• In 40-point and 60-point type FX
3G
PLCs, the variable analog potentiometer board can be connected only
to the option connector 2, and occupies the communication channel ch2.
In this case, the communication function using the communication channel ch2 is not available when the
VRRD or VRSC instruction is used.
→
For details, refer to the Communication Control Edition manual.
S
1
S
M8000
RST
Z
FNC 08
FOR
K8
FNC 85
VRRD
K0Z
D200Z
Z
M8000
FNC 24
INC
FNC 09
NEXT
RUN
monitor
X000
T0
D200
T0
Y000
X001
T1
D201
T1
Y001
X007
T7
D207
T7
Y007
Because T0 to T7 are 100
ms timers, 0 to 25.5 sec are
obtained from the set values
0 to 255.
The index register Z is reset.
The routine "FOR ~ NEXT" is repeated 8 times.
Z + 1
→
Z
Analog values of variable
potentiometers are stored in data
registers D200 to D207.
0
4
7
16
17
21
23
27
59
63
Analog timer of VR0
Analog timer of VR1
Analog timer of VR7