![Mitsubishi Electric MELSEC FX3G Скачать руководство пользователя страница 934](http://html.mh-extra.com/html/mitsubishi-electric/melsec-fx3g/melsec-fx3g_programming-manual_239083934.webp)
932
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.1 States and Colors of LEDs PLC Operation Status
38. Error Check Method and Error Code List
When an error occurs while the program is being executed, troubleshoot the cause of the error in accordance
with this chapter.
For error details, refer to the Data Communication Edition and the Hardware Edition of the PLC main unit.
38.1
States and Colors of LEDs PLC Operation Status
When an error has occurred, the PLC state can be checked using the LED status lights on the PLC.
38.1.1 POWER (POW) LED [lit, flickering or unlit] [FX
3G
/FX
3U
/FX
3UC
]
LED status
PLC status
Action
Lit
The voltage is correctly supplied to the power
terminal.
The power supply is normal.
Flickering
One of the following has occurred:
• The voltage or current is incorrectly
supplied to the power terminal.
• The wiring is incorrect.
• There is fault inside the PLC.
• Check the power supply voltage.
• Disconnect cables except the power cable, turn the PLC
power ON again, and check whether the status is
changed.
If the status is not improved, consult a Mitsubishi Electric
Distributor.
Unlit
One of the following has occurred:
• The power is OFF.
• The voltage is incorrectly supplied to the
power terminal.
• There is a break in the power cable.
When the power is not OFF, check the power supply and
power line route.
When the power is correctly supplied, consult a Mitsubishi
Electric Distributor.
POWER(Green)
RUN(Green)
BATT(Red)
ERROR(Red)
ERROR(Red)
POWER
(Green)
RUN(Green)
ALM (Red)
FX
3U
PLC
FX
3UC
(D, DSS) PLC
POWER(Green)
RUN(Green)
BATT(Red)
ERROR(Red)
FX
3UC
-32MT-LT(-2) PLC
ERROR(Red)
POWER
(Green)
RUN(Green)
BATT(Red)
L.RUN(Green)
L.ERR
(Red)
FX