Buffer Memory (BFM) 7
7-1
7
7.
Buffer Memory (BFM)
Each setting and alarm in the FX
2N
-2LC is written from or read to the PLC main unit through
buffer memories (hereafter referred to as "BFM").
Each BFM consists of 16 bits. Use FROM/TO instructions in the 16-bit format.
7.1
Buffer memory list
Table 7.1:
BFM No.
Name
Description/set range
Initial
value
Remarks
CH1 CH2
#0
Flag
Error flag, ready flag, etc.
0
R
---
#1
#2
Event
Alarm status, temperature rise
completed status, etc.
0
#3
#4
Measured value (PV)
±5% of input range (
°
C/
°
F)
0.0
#5
#6
Control output value (MV)
-5.0 to 105.0 (%)
-5.0
#7
#8
Heater current measured value
0.0 to 105.0 (A)
0.0
#9
Initialization command
0: Performs nothing
1: Initializes all data
2: Initializes BFM #10 to BFM #69
0
R/W
#10
Error reset command
0: Performs nothing
1: Resets errors
0
#11
Control start/stop changeover
0: Stops control
1: Starts control
0
#12
#21 Set value (SV)
Within set range limiter
0.0
✩
#13
#22 Alarm 1 set value
Unit:
°
C or
°
F
Allowable set range varies
depending on alarm mode set-
ting.
0.0
#14
#23 Alarm 2 set value
0.0
#15
#24 Alarm 3 set value
0.0
#16
#25 Alarm 4 set value
0.0
#17
#26
Heater disconnection alarm set
value
0.0 to 100.0 A
(When "0.0" is set, alarm function
is disabled.)
0.0
#18
#27 Auto/manual mode changeover
0:AUTO 1:MAN
0
#19
#28 Manual output set value
-5.0 to 105.0 (%) *1
0.0
#20
#29 Auto tuning execution command
0: Stops auto tuning
1: Performs auto tuning
0
#30
Unit type code
2060
R
---
#31
Prohibited
---
---
---
#32
#51 Operation mode
0: Monitor
1: M Temperature alarm
2: M Temperature alarm +
Control
2
R/W
✩
#33
#52 Proportional band
0.0 to 1,000.0 %/span
(When "0.0" is set, two-position
control is performed.)
3.0
#34
#53 Integral time
1 to 3,600 sec
240
#35
#54 Derivative time
0 to 3,600 sec
60
FX2N-2LC Temperature Control Block
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...