FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-26
7.2.36
BFM #77: Number of times of alarm 1/2/3/4 delay
In BFM #77, set the number of alarm delays. This setting is applied to all alarms 1 to 4.
The alarm delay function keeps the non-alarm status until the number of input samples
exceeds the number of alarm delays, after the deviation between the measured value (PV) and
the set value (SV) reaches the alarm set value.
If the deviation remains in the alarm range until the number of input samples exceeds the num-
ber of alarm delays, an alarm is issued.
The allowable set range is from 0 to 255 times. (input sampling cycle: 500 ms)
Example: When the number of alarm delays, is set to 5 times
7.2.37
BFM #78: Number of times of heater disconnection alarm delay
In BFM #78, set the number of heater disconnection alarm delays. This setting is applied to
both CH1 and CH2.
If the abnormal status consecutively occurs in the heater current measured value (sampling
cycle: 1 sec) by the preset number of times, an alarm is issued.
The allowable set range is from 3 to 255 times.
Temperature
set value (SV)
Alarm status
Alarm status
Non-alarm status
Time
Measured value
(PV)
Measured value (PV)
Alarm set value
Input sampling
3 times
5 times
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...