Introduction of Functions 5
5-3
5
5.2
Two-position control
When the proportional band (P) value is set to "0.0", the FX
2N
-2LC performs two-position con-
trol.
In two-position control, the control output (MV) is set to ON when the measured value (PV) is
larger than the temperature set value (SV) or OFF when the measured value (PV) is smaller
than the temperature set value (SV).
When the adjustment sensitivity (dead zone) is set, repetitious turning ON/OFF of the output
around the temperature set value (SV) can be prevented.
However, if the adjustment sensitivity (dead zone) is set to a large value, upward/downward
fluctuation becomes large accordingly. If the adjustment sensitivity (dead zone) is set to a
small value, chattering (drastic repetitious turning ON/OFF) may be caused by small oscilla-
tions of measured values.
Temperature
set value (SV)
Operation output
value (MV)
Adjustment sensitivity (dead zone)
ON
OFF
ON
OFF
Time
* The adjustment sensitivity is equally given
to the upper portion and the lower portion
of the temperature set value (SV).
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...