FX2N-2LC Temperature Control Block
Program Example 8
8-7
8
•
In this example, the status of the flags (BFM #0) and the events (BFM #1 and BFM #2) can
be monitored using auxiliary relays (M). In order to output such status to the outside, use
each auxiliary relay as a contact and drive outputs (Y).
M0
Y 0
M28
Y 1
M48
Y 2
An error is present.
CH1 loop is disconnected.
CH2 loop is disconnected.
"Error present" is output.
"CH1 loop disconnection" alarm is output.
"CH2 loop disconnection" alarm is output.
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...