FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-15
7
7.2.24
BFM #41 (CH1) and BFM #60 (CH2): Adjustment sensitivity (dead zone) setting
In BFM #41, set the adjustment sensitivity (dead zone) of CH1. In BFM #60, set the adjust-
ment sensitivity (dead zone) of CH2.
By setting the adjustment sensitivity, repetitious turning on/off of the output around the temper-
ature set value (SV) can be prevented while two-position control is performed.
The value set to BFM #41/#60 is equally given to the upper portion and the lower portion of the
temperature set value (BFM #12/#21). (For example, if the adjustment sensitivity value is set
to "10%", 5% above the temperature set value and 5% below the temperature set value are
treated as the dead zone (width of 10% in total).
The allowable set range is from 0.0 to 10.0%.
Example
Condition: When BFM #41/#60 is set to "10.0%" in the range span of 400
°
C
400
°
C x 10.0% / 100 = 40
°
C
When the temperature set value is 200
°
C, the range from 180 to 220
°
C is treated as the dead
zone.
When the adjustment sensitivity (dead zone) is set to a large value, ver tical fluctuation
becomes large.
When the adjustment sensitivity is too small, small oscillations of the measured value cause
chattering.
7.2.25
BFM #42 (CH1) and BFM #61 (CH2): Control output cycle setting
In BFM #42, set the control output cycle of CH1. In BFM #61, set the control output cycle of
CH2.
Set the period of time in which the output turns on and off.
The value set here multiplied by the control output value (%) is treated as the ON time. The
value set here multiplied by "100 - Control output value (%)" is treated as the OFF time.
The allowable set range is from 1 to 100 sec.
Temperature
set value (SV)
Control output
value (MV)
Adjustment sensitivity (dead zone)
ON
OFF
ON
OFF
Time
* The adjustment sensitivity setting
is given to both the upper portion
and the lower portion of the
temperature set value (SV).
ON
OFF
Control output cycle
Control output
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...