Diagnostic 9
9-1
9
9.
Diagnostic
By reading the flags (BFM #0) and the events (BFM #1 and BFM #2) using FROM instructions,
you can confirm errors (such as lack of the driving power supply 24 V, heater disconnection
and loop breaking) which can be recognized by the FX
2N
-2LC.
Events (BFM #1 and BFM #2) indicating errors
When an error above has occurred, the contents described in the corresponding "Description"
column may be causes.
Eliminate causes of errors, then reset all errors using BFM #10.
If causes of an error remain, the corresponding bit turns on again.
Table 9.1: Flags (BFM #0) indicating errors
Bit No.
Description
Operation
b0
Error present
Turns on when an error among b1 to b10 below has occurred.
b1
Set value range error
Turns on when data outside set range is written.
b2
24 VDC power supply
error
Turns on when driving power supply (24 VDC) is not supplied.
b3
Set value backup error
Turns on when an error has been caused by noise or when a fail-
ure has occurred in FX
2N
-2LC.
If contents of error are not eliminated even after power is turned
off once then on again, contact Mitsubishi Electric System Ser-
vice.
··
·
··
·
··
·
b8
Sum check error for
adjustment data error
Turns on when an error has been caused by noise or when a fail-
ure has occurred in FX
2N
-2LC.
If contents of error are not eliminated even after power is turned
off once then on again, contact Mitsubishi Electric System Ser-
vice.
b9
Cold contact temperature
compensation data error
b10
A/D converted value error
Table 9.2: Events (BFM #1 and BFM #2) indicating errors
Bit No.
Assignment
Description
b0
Input error (upper limit)
Turns on when input value is over scale.
b1
Input error (lower limit)
Turns on when input value is under scale.
b2
Cold contact temperature
compensation data error
Turns on when an error has been caused by noise or when a fail-
ure has occurred in FX
2N
-2LC.
If contents of error are not eliminated even after power is turned
off once then on again, contact Mitsubishi Electric System Ser-
vice.
b3
A/D converted value error
b4
Alarm 1
Turns on when an alarm has occurred.
b5
Alarm 2
Turns on when an alarm has occurred.
b6
Alarm 3
Turns on when an alarm has occurred.
b7
Alarm 4
Turns on when an alarm has occurred.
b8
Loop breaking alarm
Turns on when a loop breaking alarm has occurred.
b9
Heater disconnection
alarm
Turns on when a heater disconnection alarm has occurred.
b10
Heater meltdown alarm
Turns on when a heater meltdown alarm has occurred.
FX2N-2LC Temperature Control Block
Содержание MELSEC FX2N-2LC
Страница 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Страница 4: ...FX2N 2LC Tempereture Control Block ii ...
Страница 6: ...FX2N 2LC Tempereture Control Block iv ...
Страница 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Страница 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Страница 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Страница 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Страница 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Страница 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Страница 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Страница 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Страница 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Страница 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Страница 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Страница 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Страница 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Страница 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...