7 CC-Link IE Field Network Basic FUNCTION
7.1 Cyclic Transmission
79
7
Link scan time after timeout
If a timeout occurs due to the failure of a slave device, the link scan time will be changed depending on the setting value of the
timeout time.
• When the timeout time is shorter than the link scan time, operation follows the configured "Link Scan Time". (
• When the timeout time is longer than the link scan time, operation follows the "Timeout time" configured for "Link scan
settings". (
To minimize the effect of communication transmission delays with normal slave stations during a timeout,
adjust the timeout time. For example, using CC-Link IE Field Network Basic diagnosis, check the current link
scan time (when all slave stations are operating normally), and then set a timeout time about five times as
long as the link scan time. (When the current link scan time is 10 ms, set 50 ms for the timeout time.)
■
If the master station receives a faulty response from a slave station
The master station immediately disconnects that slave station regardless of the timeout period and disconnection detection
count set in link scan settings. The corresponding slave station generates a data link error. (The error code will be generated
by the slave station.)
The following table shows the operations of special relays and special registers when a slave station is disconnected.
Some slave stations are equipped with a function that makes them disconnected without being an error
station. For details, refer to the manual of the slave station used. (Since the slave station does not become an
error station, 'Data link status' (SM1540) and 'Data link status of each station' (SD1540 to SD1543) do not
change.)
Special relay, special register
Operation
'Cyclic transmission status' (SM1536)
The device remains ON.
'Cyclic transmission status of each station' (SD1536
to SD1539)
The bit corresponding to the station number of the disconnected slave station turns OFF.
'Data link status' (SM1540)
OFF to ON
'Data link status of each station' (SD1540 to
SD1543)
The bit corresponding to the station number of the disconnected slave station turns ON (indicating that
the slave station is an error station).
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......