![Mitsubishi Electric MELIPC MI5000 Series Скачать руководство пользователя страница 236](http://html.mh-extra.com/html/mitsubishi-electric/melipc-mi5000-series/melipc-mi5000-series_user-manual_239727236.webp)
234
APPX
Appendix 2 List of Error Codes
41E0H
File related error
There is an error with the specified drive
(memory), or this does not exist.
Back up the data of the /ROM folder, and
then initialize the memory.
41E7H
File related error
The format information data of the specified
drive (memory) is abnormal.
Back up the data of the /ROM folder, and
then initialize the memory.
41E8H
File related error
The format information data of the specified
drive (memory) is abnormal.
Back up the data of the /ROM folder, and
then initialize the memory.
41E9H
File related error
The specified file is being accessed.
Execute it again after a while.
41EBH
File related error
There is an error in the specification method
of the file name.
Check the file name, and execute the
request again.
41ECH
File related error
The file system of the specified drive
(memory) is logically corrupted.
Back up the data of the /ROM folder, and
then initialize the memory.
41EDH
File related error
The specified drive (memory) does not have
enough continuous free space. (There is
free space for the file, but the continuous
free space is insufficient.)
Delete unnecessary files, and then execute
again.
41F3H
File related error
The size of the specified file exceeds 4 GB
minus 2 bytes.
Reduce the size of the specified file through
creation or a size change. Alternatively,
separate the file into multiple files to reduce
the file size.
4A02H
Link-related error
The specified station cannot be accessed.
Check that the operating mode is not set to
offline.
Check that there are no mistakes in the
network No. or station No. settings.
4A03H
Link-related error
A request for network test was issued.
Check request data such as SLMP.
4B00H
Target related
An error occurred on the access destination
or the relay station. Alternatively, the
specified connection destination (request
destination module I/O number) is not
supported.
• Check the error occurred on the specified
access destination or relay station to the
station to be accessed, and take the
corrective actions.
• Check the request data connection
destination settings (request destination
module I/O number).
• Check the stop error, and take the
corrective actions.
4B02H
Target related
There is no request addressed to the
MELIPC.
Perform the operation to the module that
can perform the specified function.
4B03H
Target related
• The specified route is not supported by
the version of the specified MELIPC.
• The CPU of the communication target is
not mounted.
• A device that does not support
communications is on the specified route.
• Check the specified route.
• Check the mounting status of the CPU
module.
• Check the stop error, and take the
corrective actions.
4B04H
Target related
The specified connection destination
(request destination module I/O number) is
not supported.
In other device settings, an illegal value is
set for the target module header I/O
number. Change to a header I/O number for
an existing unit, and carry out
communications again.
Error code
Error name
Description
Corrective action
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......