Appendix 2 List of Error Codes
■
CC-Link IE Field Network error codes (D000H to DFFFH)
The following shows the codes for errors that occur on CC-Link IE Field Network.
Error code
Error name
Description
Corrective action
D000H
CC-Link IE Field Network function
related errors
MELIPC error detected.
Consult your local Mitsubishi
representative.
D041H
CC-Link IE Field Network function
related errors
Communications station number error.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If there are in excess of 120 slave
stations on 1 network, then reduce this to
120 or less.
D080H to D083H
CC-Link IE Field Network function
related errors
MELIPC error detected.
Consult your local Mitsubishi
representative.
D0A0H
CC-Link IE Field Network function
related errors
In transient transmission, there was a
response wait time out.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If an error is detected in own station,
target station, or relay, then confirm the
source of the error, and take measures.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
D0A1H
CC-Link IE Field Network function
related errors
In transient transmission, there was a
transmit end wait time out.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If an error is detected in own station,
target station, or relay, then confirm the
source of the error, and take measures.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
D0A2H
CC-Link IE Field Network function
related errors
In transient transmission, there was a
transmit processing wait time out.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
D0A3H
CC-Link IE Field Network function
related errors
Transient transmission processing was not
carried out correctly.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If an error is detected in own station,
target station, or relay, then confirm the
source of the error, and take measures.
• Correct the transient data target station
No., and run again.
D0A4H to D0A6H
CC-Link IE Field Network function
related errors
Transient transmission failed.
• Check that there are no faults with the
request source cable or a switching hub
connections.
• Lower the transient transmission usage
frequency, and then perform again.
D0C0H
CC-Link IE Field Network function
related errors
During reserved station specification
processing, reserved station specification
was performed again.
Wait some time before again carrying out
reserve station specification.
D0C1H
CC-Link IE Field Network function
related errors
During reserved station temporary clear
specification processing, reserved station
temporary clear specification was
performed again.
Wait some time before again carrying out
reserve station temporary clear
specification.
D0C4H
CC-Link IE Field Network function
related errors
During temporary error disabled station
settings processing, temporary error
disabled station settings were performed
again.
Wait some time before again carrying out
temporary error disabled station settings.
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......