Appendix 2 List of Error Codes
D281H
CC-Link IE Field Network function
related errors
Transient reception failed.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If target station or relay station transient
data reception is overloaded, then have
the transmission source transmit after a
certain time has elapsed.
D282H
CC-Link IE Field Network function
related errors
Reception queue full.
• Temporarily interrupt transient
transmission, and try again.
• Lower the transient transmission usage
frequency, and then perform again.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
D283H
CC-Link IE Field Network function
related errors
Transient transmission failed.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• Lower the transient transmission usage
frequency, and then perform again.
D284H
CC-Link IE Field Network function
related errors
Error in the SLMP target execution module.
Correct the target execution module in the
SLMP header, and run again.
D2A0H
CC-Link IE Field Network function
related errors
Reception buffer full.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If target station or relay station transient
data reception is overloaded, then have
the transmission source transmit after a
certain time has elapsed.
D2A1H
CC-Link IE Field Network function
related errors
Transmission buffer full.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
D2A2H
CC-Link IE Field Network function
related errors
In transient transmission, there was a
transmit end wait time out.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
D2A3H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
data length.
Correct the data quantity (frame length) at
the transient request source, and run again.
D2A4H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
header information.
Correct the header information at the
transient request source, and run again.
D2A5H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
target station number.
Correct the target station No. at the
transient request source, and run again.
D2A6H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
request source number.
Correct the request source number at the
transient request source, and run again.
D2A7H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
header information.
Correct the header information at the
transient request source, and run again.
D2A8H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
header information.
Correct the header information at the
transient request source, and run again.
D2A9H
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
target network number.
Correct the target network number at the
transient request source, and run again.
D2AAH
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
target station number.
Correct the target station No. at the
transient request source, and run again.
D2ABH
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
request source network number.
Correct the request source network number
at the transient request source, and run
again.
D2ACH
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
request source station number.
Correct the request source station number
at the transient request source, and run
again.
D2ADH
CC-Link IE Field Network function
related errors
Error in the transient transmission frame
data length.
Correct the data quantity (frame length) at
the transient request source, and run again.
Error code
Error name
Description
Corrective action
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......