278
APPX
Appendix 8 List of Link Special Registers
SW0100 to
SW0107
Each station CPU moderate/major error
occurrence status
The local station stores each station CPU module moderate and major error occurrence status.
Remote I/O station, remote device station, and intelligent device station stores the moderate/major
error occurrence status of each station.
• 0: No moderate or major error
• 1: Moderate or major errors occurring
The numbers within the following illustration indicate the station numbers. (
: fixed at 0)
<Conditions>
• Enabled when 'baton pass status' of own station (SB0047) is OFF.
• When 'baton pass status of own station' (SB0047) is ON (error), the data immediately before is
retained.
• Only enabled for stations with normal 'each station baton pass status' (SW00A0 to SW00A7).
• The status is not stored for the reserved stations and the station numbers after the maximum station
number.
SW108 to
SW10F
Station number duplication occurrence
status
Shows duplication of station numbers.
• 0: No duplication in station number
• 1: Duplicate in one or more station numbers
The numbers within the following illustration indicate the station numbers. (
: fixed at 0)
SW0110 to
SW0117
Each station CPU minor error
occurrence status
The local station stores each station CPU module minor error occurrence status.
Remote I/O station, remote device station, and intelligent device station stores the minor error
occurrence status of each station.
• 0: Normal, or moderate or major errors occurring
• 1: Minor error
The numbers within the following illustration indicate the station numbers. (
: fixed at 0)
<Conditions>
• Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
• Only enabled for stations with normal 'each station baton pass status' (SW00A0 to SW00A7).
• The status is not stored for the reserved stations and the station numbers after the maximum station
number.
No.
Name
Description
b15
b0
16 15 14 13 12
5
4
3
2
1
32 31 30 29 28
21 20 19 18 17
SW0100
112 111 110 109 108
102 101 100 98 97
-
-
-
-
-
117 116 115 114 113
SW0101
SW0106
SW0107
~
~
~
~
~
b15
b0
16 15 14 13 12
5
4
3
2
1
32 31 30 29 28
21 20 19 18 17
SW0108
112 111 110 109 108
102 101 100 98 97
-
-
-
-
-
117 116 115 114 113
SW0109
SW010E
SW010F
~
~
~
~
~
b15
b0
16 15 14 13 12
5
4
3
2
1
32 31 30 29 28
21 20 19 18 17
SW0110
112 111 110 109 108
102 101 100 98 97
-
-
-
-
-
117 116 115 114 113
SW0111
SW0116
SW0117
~
~
~
~
~
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......