204
APPX
Appendix 1 Troubleshooting by Symptom
Ethernet communications to the VxWorks part are not possible
Issue a ping from the PC to the product, and confirm the response.
If abnormal ping response
If normal ping response
An error may have occurred with communications of applications in use. This section shows troubleshooting of applications
compatible with this product.
■
If MI Configurator cannot connect
■
If CW Workbench 4 cannot connect
Check item
Corrective action
Is the Ethernet cable wired correctly?
Correctly wire the Ethernet cable.
Is the Ethernet cable broken?
Replace the Ethernet cable.
Are the PC and product IP address segments different?
• Change the PC and product IP addresses to the same segments.
• If through a LAN on a different segment via a gateway, consult with the
connected LAN network administrator.
On the connected LAN, are there any duplicate IP addresses with the product
and PCs?
Consult with the administrator of the connected LAN, and ensure that there
are no duplicated IP addresses.
Has the product been replaced?
Reset all terminals connected to the network.
Is the network under high load?
• Consult with the administrator of the connected LAN and disconnect
devices connected by Ethernet that may cause a high load.
• Change the connection of the personal computer and this product to a
different network.
Is the specified IP address correct?
Specify the correct IP address.
In the following settings, is access from the PC being blocked?
• [Basic Parameter]
[External Device Cooperate Applicable Settings]
[Security Settings]
[IP Filter Settings]
In the IP filter settings, unblock access from the PC.
Check item
Corrective action
Is the connection destination of MI Configurator is set to a different route?
Change the connection destination setting of MI Configurator to the correct
route.
Is an Ethernet cable connected to the Ethernet port (CH1)?
Change the connection destination of the Ethernet cable to the Ethernet port
(CH1), and set so that Ping provides a normal response.
In the following settings, is access from the PC being blocked?
• [Basic Parameter]
[External Device Cooperate Applicable Settings]
[Security Settings]
[IP Filter Settings]
In the IP filter settings, unblock access from the PC.
Check item
Corrective action
Is an Ethernet cable connected to the Ethernet port (CH1)?
Change the connection destination of the Ethernet cable to the Ethernet port
(CH1), and set so that Ping provides a normal response.
"Target Server Options" of CW Workbench 4 is not set properly.
Set "Target Server Options" of CW Workbench 4 properly.
In the following settings, is access from the PC being blocked?
• [Basic Parameter]
[External Device Cooperate Applicable Settings]
[Security Settings]
[IP Filter Settings]
In the IP filter settings, unblock access from the PC.
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......