226
APPX
Appendix 2 List of Error Codes
3E41H
System WDT error
• The system watchdog timer managed by
the system detected an error.
Alternatively, an error occurred in system
software.
• The system WDT monitoring time is
short.
• Tasks with the higher CPU usage rate is
in operation.
• A program causing an error in the
memory or stack was executed.
• The operation that increase the CPU
usage rate of the system task (writing
parameter) was performed.
• The station on which the station-based
block data assurance setting is enabled
on the network has been accessed when
the stop error occurred.
• MELIPC is uncontrollable or damaged
(malfunction from noise, or hardware
fault).
• BIOS settings screen started.
• Reset the system. Lower the CPU
utilization of tasks with high CPU
utilization. Alternatively, do not run them.
• Review the user program.
• Set a sufficiently long system WDT
monitoring time after consideration of the
CPU utilization of the system tasks.
• Review the user program to prevent the
station on which the station-based block
data assurance setting is enabled from
being accessed when the stop error
occurred.
• Take measures to reduce noise.
• Confirm that the ambient environment is
within general specifications.
• When starting this product, ensure that
the BIOS settings screen does not start.
If the same error is displayed again, this
may indicate a hardware fault. Consult your
local Mitsubishi representative.
3E42H
System WDT error
The system watchdog timer managed by
the system detected an error. Alternatively,
an error occurred in system software.
• The system WDT monitoring time is
short.
• Tasks with the higher CPU usage rate is
in operation.
• A program causing an error in the
memory or stack was executed.
• The operation that increase the CPU
usage rate of the system task (writing
parameter) was performed.
• The station on which the station-based
block data assurance setting is enabled
on the network has been accessed when
the stop error occurred.
• An error was detected in the memory.
• MELIPC is uncontrollable or damaged
(malfunction from noise, or hardware
fault).
• Reset the system.
• Lower the CPU usage rate of tasks with
the higher rate, or make them inactivated.
• Review the user program.
• Set a sufficiently long system WDT
monitoring time after consideration of the
CPU utilization of the system tasks.
• Review the user program to prevent the
station on which the station-based block
data assurance setting is enabled from
being accessed when the stop error
occurred.
• Take measures to reduce noise.
• Confirm that the ambient environment is
within general specifications.
If the same error is displayed again, this
may indicate a hardware fault. Consult your
local Mitsubishi representative.
3E46H
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3E47H
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3E4BH
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3E4CH
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3E4EH
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
Error code
Error name
Description
Corrective action
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......