3EA2H
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3EA4H
Hardware failure
A hardware failure was detected.
Exchange the MELIPC.
3EA6H
Hardware failure
A hardware failure resulting from a MELIPC
temperature error was detected.
Immediately turn the power OFF, and take
the following measures.
• Check the ambient temperature.
• Check that the vent of the MELIPC is not
blocked.
• Inspect and clean the fan module.
• Replace the fan module.
• If the same error is displayed again, this
may indicate a hardware fault. Consult
your local Mitsubishi representative.
3EA7H
Hardware failure
A hardware failure was detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3EA8H
Hardware failure
A hardware failure has been detected.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
3EA9H
Memory error
An error was detected in the memory.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
Error code
Error name
Description
Corrective action
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......