123
Extended parametersExtended parameters
Extended p
a
ramete
r
li
s
t
En
ergy saving monit
o
r
891
Refer to
Pr.52
.
892
Load factor
0.1%
100%
30 to 150%
Set the load factor for commercial power-
supply operation.
This value is used to calculate the power
consumption estimated value during
commercial power supply operation.
893
Energy saving
monitor reference
(motor capacity)
0.01/
0.1kW
*16
LD/SLD
value of
Applied
moter
Capacity
0.1 to 55/
0 to 3600kW
*16
Set the motor capacity (pump capacity).
Set when calculating power saving rate
and average power saving rate value.
*16 The setting depends on the inverter
capacity (200V class and FR-F740-
01160 or less/FR-F740-01800 or more)
894
Control selection
during commercial
power-supply
operation
1
0
0
Discharge damper control (fan)
1
Inlet damper control (fan)
2
Valve control (pump)
3
Commercial power-supply drive (fixed
value)
895
Power saving rate
reference value
1
9999
0
Consider the value during commercial
power-supply operation as 100%
1
Consider the
Pr.893
setting as 100%.
9999
No function
896
Power unit cost
0.01
9999
0 to 500
Set the power unit cost. Display the power
saving rate on the energy saving monitor
9999
No function
897
Power saving
monitor average
time
1
9999
0
Average for 30 minutes
1 to 1000h
Average for the set time
9999
No function
898
Power saving
cumulative monitor
clear
1
9999
0
Cumulative monitor value clear
1
Cumulative monitor value hold
10
Cumulative monitor continue
(communication data upper limit 9999)
9999
Cumulative monitor continue
(communication data upper limit 65535)
899
Operation time rate
(estimated value)
0.1%
9999
0 to 100%
Use for calculation of annual power
saving amount. Set the annual operation
ratio (consider 365 days
×
24hr as 100%).
9999
No function
A
d
just
ment
of
te
rminal CA
and AM
(c
al
ibrat
ion)
C0
(900)
CA terminal
calibration
---
---
---
Calibrate the scale of the meter
connected to terminal CA.
×
C1
(901)
AM terminal
calibration
---
---
---
Calibrate the scale of the analog meter
connected to terminal AM.
×
———
C2
(902)
Terminal 2 frequency
setting bias frequency
Refer to
Pr.125 and Pr.126
.
C3
(902)
Terminal 2 frequency
setting bias
C4
(903)
Terminal 2 frequency
setting gain
C5
(904)
Terminal 4 frequency
setting bias frequency
C6
(904)
Terminal 4 frequency
setting bias
C7
(905)
Terminal 4 frequency
setting gain
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled
Содержание FR-F700 Series