38
Operation by the start command from
the operation panel (PU operation mode)
3.5.4
Perform frequency setting by analog (voltage input)
[Connection diagram]
(The inverter supplies 5V of power to the frequency setting potentiometer.(Terminal 10))
POINT
· Use
/
to give a start command.
·
Pr. 79 Operation mode selection
must be set to "4" (external/PU combined operation mode 2)
Three-phase
AC power supply
Motor
Frequency setting
potentiometer
Inverter
R/L1
S/L2
T/L3
U
V
W
5
10
2
FR-DU07
,
Display
Operation
CAUTION
When both the forward switch and reverse
switch turn on, the inverter will not start.
Also, if both switch turn on while running,
the inverter stops.
Flicker ··· Parameter setting complete!!
Flickering
( )
The parameter number
read previously appears.
8.
Start
Press the start switch (or ).
Operation status indication of FWD (or REV)
flickers.
1.
Screen at powering on
The monitor display appears.
2.
Press to choose the parameter setting
mode.
3.
Turn until (
Pr. 79
) appears.
4.
Press to read the currently set value.
" "(initial value) appears.
5.
Turn clockwise to change it to the setting
value of " ".
7.
Mode/monitor check
Press twice to choose the
monitor/frequency monitor.
6.
Press to set.
9.
Acceleration
→
constant speed
Turn the volume (frequency setting
potentiometer) clockwise slowly to full.
The frequency value on the indication
increases according to
Pr. 7
Acceleration
time
until 60Hz is displayed.