112
Extended parametersExtended parameters
Extended p
a
ramete
r
li
s
t
Com
m
unica
ti
on
init
ial s
e
tt
ing
342
Communication
EEPROM write
selection
1
0
0
Parameter values written by
communication are written to the EEPROM
and RAM.
1
Parameter values written by
communication are written to the RAM.
343
Communication
error count
1
0
(read only)
Display the number of communication
errors during Modbus-RTU communication.
Read only.
Displayed only when Modbus-RTU protocol
is selected.
×
×
×
549
Protocol selection
1
1
0
Mitsubishi inverter
(computer link)
protocol
After setting
change, reset
(switch power off,
then on) the
inverter.
The setting change
is reflected after a
reset.
1
Modbus-RTU
protocol
Chan
ge of
analog
input
f
re
quency
,
adj
us
tm
ent
of
volt
age,
cur
rent
input
and f
requenc
y (calibrat
ion)
125
Terminal 2
frequency setting
gain frequency
0.01Hz
60Hz
0 to 400Hz
Set the frequency of terminal 2 input gain
(maximum).
×
126
Terminal 4
frequency setting
gain frequency
0.01Hz
60Hz
0 to 400Hz
Set the frequency of terminal 4 input gain
(maximum).
×
241
Analog input display
unit switchover
1
0
0
Displayed in %
Select the unit for
analog input display.
1
Displayed in V/mA
C2
(902)
Terminal 2
frequency setting
bias frequency
0.01Hz
0Hz
0 to 400Hz
Set the frequency on the bias side of
terminal 2 input.
×
C3
(902)
Terminal 2
frequency setting
bias
0.1%
0%
0 to 300%
Set the converted % of the bias side
voltage (current) of terminal 2 input.
×
C4
(903)
Terminal 2
frequency setting
gain
0.1%
100%
0 to 300%
Set the converted % of the gain side
voltage of terminal 2 input.
×
C5
(904)
Terminal 4
frequency setting
bias frequency
0.01Hz
0Hz
0 to 400Hz
Set the frequency on the bias side of
terminal 4 input.
×
C6
(904)
Terminal 4
frequency setting
bias
0.1%
20%
0 to 300%
Set the converted % of the bias side
current (voltage) of terminal 4 input.
×
C7
(905)
Terminal 4
frequency setting
gain
0.1%
100%
0 to 300%
Set the converted % of the gain side
current (voltage) of terminal 4 input.
×
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled