115
Extended parametersExtended parameters
Extended p
a
ramete
r
li
s
t
Param
e
te
r unit
langua
ge sw
it
chov
er
145
PU display
language selection
1
1
0
Japanese
×
×
1
English
2
Germany
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
—
148,149
Refer to
Pr.22 and Pr.23
.
Det
e
ct
ion of
out
put
curren
t (Y12 signal)
Det
e
c
tion of
zero curr
ent
(Y13 signal)
150
Output current
detection level
0.1%
110%
0 to 120%
Set the output current detection level.
100% is the rated inverter current.
151
Output current
detection signal
delay time
0.1s
0s
0 to 10s
Set the output current detection period.
Set the time from when the output current
has risen above the setting until the output
current detection signal (Y12) is output.
152
Zero current
detection level
0.1%
5%
0 to 150%
Set the zero current detection level.
Suppose that the rated inverter current is
100%.
153
Zero current
detection time
0.01s
0.5s
0 to 1s
Set this parameter to define the period
from when the output current drops below
the
Pr.152
value until the zero current
detection signal (Y13) is output.
166
Output current
detection signal
retention time
0.1s
0.1s
0 to 10s
Set the retention time when the Y12
signal is on.
9999
The Y12 signal on status is retained.
The signal is turned off at the next start.
167
Output current
detection operation
selection
1
0
0
Operation continues when the Y12 signal
is on
1
The inverter is brought to an alarm stop
when the Y12 signal is on. (E.CDO)
—
154
Refer to
Pr.22 and
Pr.23
.
Select
io
n of
ac
ti
on
co
ndi
ti
ons of
t
h
e
s
e
cond f
u
nc
ti
on
155
RT signal reflection
time selection
1
0
0
This function is immediately made valid
with on/off of the RT signal.
10
The on/off of the RT signal is valid only
during a stop and constant speed
operation. (Invalid during acceleration/
deceleration)
—
156, 157
Refer to
Pr.22 and Pr.23
.
158
Refer to
Pr.54 to Pr.56
.
159
Refer to
Pr.135 to Pr.139
.
Display
of
applied
p
a
ra
met
e
rs and
us
er
group f
unc
ti
on
160
User group read
selection
1
0
9999
Only the simple mode parameters can be
displayed.
1
Only the parameters registered in the user
group can be displayed.
0
Simple mode and extended mode
parameters can be displayed.
172
User group
registered display/
batch clear
1
0
(0 to 16)
Displays the number of cases registered as
a user group (reading only).
×
×
9999
Batch clear the user group registration
173
User group
registration
1
9999
0 to 999,
9999
Set the parameter numbers to be
registered to the user group.
Read value is always "9999".
×
×
174
User group clear
1
9999
0 to 999,
9999
Set the parameter numbers to be cleared
from the user group.
Read value is always "9999".
×
×
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Param
eter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
me
te
rs
: enabled
×
: disabled