17
Wiring
2
INS
T
ALLA
TIO
N
A
ND
WIRING
(2) Output signals
F
re
que
nc
y set
ti
ng
10E
Frequency
setting
power
supply
When connecting the frequency setting potentiometer at an
initial status, connect it to terminal 10.
Change the input specifications when connecting it to terminal
10E.
(Refer to Pr.73 Analog input selection in the Instruction
Manual (applied).)
DC10V
Permissible load
current 10mA
Instruction
Manual
(applied).
10
DC5V
Permissible load
current 10mA
38, 46
2
Frequency
setting
(voltage)
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the
maximum output frequency at 5V (10V, 20mA) and makes
input and output proportional. Use Pr.73 to switch from among
input 0 to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.
Voltage input:
Input resistance
10k
Ω
± 1k
Ω
Maximum
permissible
voltage 20VDC
Current input:
Input resistance
250
Ω
± 2%
Maximum
permissible
current 30mA
38, 46
4
Frequency
setting
(current)
Inputting 0 to 20mADC (or 0 to 5V, 0 to 10V) provides the
maximum output frequency at 20mA (5V, 10V) makes input
and output proportional. This input signal is valid only when the
AU signal is on (terminal 2 input is invalid). Use Pr.267 to
switch between the input 0 to 20mA (initial value) and 0 to
5VDC, 0 to 10VDC.
(Refer to the Instruction Manual (applied).)
40, 48
1
Frequency
setting
auxiliary
Inputting 0 to 5 VDC or 0 to 10VDC adds this signal to terminal
2 or 4 frequency setting signal. Use
Pr.73
to switch between
the input 0 to ±5VDC and 0 to ±10VDC (initial setting).
Input resistance
10k
Ω
± 1k
Ω
Maximum
permissible voltage
± 20VDC
Instruction
Manual
(applied).
5
Frequency
setting
common
Common terminal for frequency setting signal (terminal 2, 1 or
4) and analog output terminal AM. Do not ground.
--------------------
------
Ty
p
e
Terminal
Symbol
Terminal
Name
Description
Rated
Specifications
Refer to
Re
la
y
A1,
B1,
C1
Relay output 1
(alarm output)
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Abnormal: No conduction across B-C (Across A-C
Continuity), Normal: Across B-C Continuity (No conduction
across A-C)
Contact
capacity:
230VAC 0.3A
(Power
factor=0.4)
30VDC 0.3A
Instruction
Manual
(applied).
A2,
B2,
C2
Relay output 2
1 changeover Contact output
Instruction
Manual
(applied).
O
p
en
c
o
lle
ct
or
RUN
Inverter
running
Switched low when the inverter output
frequency is equal to or higher than the
starting frequency (initial value 0.5Hz).
Switched high during stop or DC
injection brake operation.
*1
Alarm code (4bit)
output
(Refer to the
Instruction Manual
(applied).)
Permissible load
24VDC 0.1A
(A voltage drop
is 3.4V
maximum when
the signal is on.)
Instruction
Manual
(applied).
SU
Up to
frequency
Switched low when the output frequency
reaches within the range of ±10% (initial
value) of the set frequency. Switched
high during acceleration/deceleration
and at a stop.
*1
Instruction
Manual
(applied).
OL
Overload alarm
Switched low when stall prevention is
activated by the stall prevention
function. Switched high when stall
prevention is cancelled.
*1
Instruction
Manual
(applied).
IPF
Instantaneous
power failure
Switched low when an instantaneous
power failure and under voltage
protections are activated.
*1
Instruction
Manual
(applied).
FU
Frequency
detection
Switched low when the inverter
output frequency is equal to or higher
than the preset detected frequency
and high when less than the preset
detected frequency.
*1
Instruction
Manual
(applied).
SE
Open collector
output common
Common terminal for terminals RUN, SU, OL, IPF, FU
--------------------
-----
Ty
p
e
Terminal
Symbol
Terminal
Name
Description
Rated
Specifications
Refer to
Содержание FR-F700 Series
Страница 134: ...MEMO ...