Operation by the start command from the
operation panel (PU operation mode)
REMARKS
Pr. 184 AU terminal function selection
must be set to "4" (AU signal) (initial value).
(Refer to the Instruction Manual (applied).)
Change the frequency (60Hz) at the maximum value of potentiometer (at 20mA)
Adjust the frequency in
Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 49.)
Change the frequency (0Hz) at the minimum value of potentiometer (at 4mA)
Adjust the frequency in
calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
the Instruction Manual (applied).)
Stop
Flickering
Display
Operation
10.
Deceleration
Perform 4mA input.
The frequency value on the indication
decreases according to
Pr. 8 Deceleration time
until 0.00Hz is displayed and the operation
status indication of FWD or REV flickers.
The motor stops.
11.
Stop
Press .
FWD or REV of the operation status indication
turns off.
Output of the
adjustment meter
(4 to 20mADC)
Output of the
adjustment meter
(4 to 20mADC)
9.
Acceleration
→
constant speed
Perform 20mA input.
The frequency value on the indication increases
according to
Pr. 7
Acceleration time
until 60.00Hz
is displayed.