–
195
–
'11 • PAC-T-160
E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Replace inverter PCB
* For model 200 and 250,
replace power transistor
as well
Replace inverter PCB
* For moel 200 and 250,
replace power transistor
as well
Replace compressor
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
Error code
Remote controller:
LED
Green
Red
Outdoor control PCB
Outdoor
inverter
PCB
1 time flash
Keeps flashing
Yellow or Red LED
Green
Indoor control PCB
Stays OFF
Keeps flashing
Keeps flashing
Content
Stays off or 4 times flash
Compressor startup failure (2/2)
Is it model 200 or 250?
Is the
power transistor
module OK?
YES
From previous page
Try to restart several times
Does it start?
Note: Several times restarting
may recover it, because liquid
refrigerant migrated in the
compressor could be discharged
from the compressor
Is the
inverter output OK ?
(Check by inverter
checker)
After power OFF, turn
SW10-4 of inverter PCB
ON and connect the
inverter checker.
Then power ON again
A
YES
YES
YES
NO
NO
NO
NO (inverter PCB anomaly)
Содержание FDF100VNVD
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...