101
-
'11 • PAC-T-160
(d) Outdoor unit fan control
1) Outdoor unit fan tap and fan motor speed
Unit: min
-1
Model
Mode
Fan motor tap
100~140
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
350
600
740
820
870
910 (950)
(2)
Heating
200
350
600
740
820
870
910 (950)
(2)
200, 250
(1)
➀
speed
➁
speed
➂
speed
➃
speed
➄
speed
➅
speed
➆
speed
Cooling/Dehumidifying
200
370
560 (600)
(3)
820
850
910
950
Heating
200
370
560 (600)
(3)
820
850
910
950
Notes (1) Fan motor speed for model 200 and 250 are same for both upper and lower fan motor.
(2) Value in ( ) are for the model 125, 140.
(3) Value in ( ) are for the model 250.
2) Fan tap control during cooling/Defumidifying operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
• Model 100 ~ 140
• Model 200, 250
zone
zone
zone
zone
zone
zone
zone
zone
zone
Tap 5
Tap 5
Tap 5
Tap 4
zone
Tap 5
Tap 5
Tap 5
Tap 4
zone
Tap 5
Tap 5
Tap 4
(1)
Tap 3
zone
Tap 5
Tap 5
Tap 4
(1)
Tap 3
zone
Tap 4
Tap 4
(1)
Tap 3
Tap 2
zone
Tap 4
Tap 4
(1)
Tap 3
Tap 2
zone
Tap 3
Tap 3
Tap 2
Tap 1
zone
Tap 3
Tap 3
Tap 2
Tap 1
Note (1) In silent mode, the fan taps are shifted from “Tap 4” to “Tap 3” for all models.
zone
zone
Outdoor air temp. (˚C)
15
18
zone
30
37
zone
46
48
zone
Outdoor unit heat exchanger temp. (˚C)
20
30
zone
33
40
zone
43
53
zone
3) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
• Model 100 ~ 140
• Model 200, 250
zone
zone
zone
zone
zone
zone
zone
Tap 3
Tap 3
Tap 4
zone
Tap 3
Tap 3
Tap 4
(1)
zone
Tap 3
Tap 4
Tap 5
zone
Tap 3
Tap 4
(1)
Tap 5
zone
Tap 4
Tap 5
Tap 6
zone
Tap 4
Tap 5
Tap 6
Note (1) In silent mode, the fan taps are shifted from “Tap 4” to “Tap 3” for all models.
3
9
12
15
-2
0
1
3
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
zone
zone
zone
zone
zone
zone
4) Outdoor unit fan control at cooling low outdoor air
a)
When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone in the cooling/dehumidifying mode, it has elapsed 20
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
Note (1) In silent mode, the fan taps are shifted from “Tap 4” to “Tap 3” for all models.
5
10
Retained
Outdoor unit fan speed
-10min
-1
20
30
Outdoor unit fan speed
+10min
-1
zone
zone
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)