-
-
'11 • PAC-T-160
PGA000Z780
Power factor
%
98
98
Inrush current
A
5 < Max.running current 24 >
Sound Pressure Level
dB(A)
P-Hi : 54 Hi : 50 Me : 48 Lo : 44
49
Exterior dimensions
Height x Width x Depth
Exterior appearance
Ceramic White
Stucco White
(Munsell color)
(N8.0) near equivalent
(4.2Y7.5/1.1) near equivalent
Net weight
kg
52
81
Refrigerant equipment
Compressor type & Q'ty
—
RMT5126MDE2 × 1
Starting method
—
Direct line start
Refrigerant oil
・
—
0.9 M-MA68
Heat exchanger
Louver fine & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 1
Propeller fan × 1
Motor <Starting method>
W
157 < Direct line start >
86 < Direct line start >
Air flow (Standard)
CMM
P-Hi : 29 Hi : 26 Me : 23 Lo : 19
Cooling : 75, Heating : 73
External static pressure
Pa
0
Outside air intake
Not possible
—
—
Air filter, Q'ty
Plastic net × 1 (Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor )
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
20 (Crank case heater)
Remote controller
RC-E4 Installed / wireless : RCN-KIT3-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Internal thermostat for fan motor
Frost protection thermostat
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
Connecting method
Flare piping
Flare piping
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant
Quantity
R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump
—
—
Drain
Insulation for piping
Necessary (both Liquid & Gas lines)
Standard Accessories
Mounting kit
Edging
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
mm
1,850 × 600 × 320
845 × 970 × 370
mm
FDF100VNVD
Indoor unit
FDF100VD
Outdoor unit
FDC100VN
Power source
220-240V~50Hz / 220V~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
10.0 [ 4.0 (Min.)~11.2 (Max.)]
11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption
kW
3.12
3.10
Running current
A
13.8 / 14.5
13.8 / 14.4
Model
Item
Adapted to
RoHS
directive
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
Hose Connectable with VP20
See page 43
Max.50m
Indoor air temperature
Operation
DB
27
o
C
20
o
C
7
o
C
6
o
C
19
o
C
35
o
C
24
o
C
WB
DB
WB
Cooling
Heating
Item
Outdoor air temperature
Liquid line: I/U
φ
9.52 (3/8") Pipe
φ
9.52 (3/8") × 0.8 O/U 9.52 (3/8")
Gas line:
φ
15.88 (5/8")
φ
15.88 (5/8") × 1.0
φ
15.88 (5/8")
Holes size
φ
20 × 3pcs
(2) Micro inverter series
(a) Single plase use
1) Single type
Содержание FDF100VNVD
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...