192
–
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
'11 • PAC-T-160
E55
Underneath temperature
thermistor anomaly
(Models FDC200, 250 only)
Keeps flashing Stays OFF
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
Models FDC200, 250
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
connection of
underneath temperature
thermistor connector
OK?
Are the
characteristics of
underneath temperature
thermistor OK?
Temperature-resistance characteristics
Temperature thermistor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
5k
Ω
at 25°C
Correct connection of
underneath temperature
thermistor connector.
Defective underneath
temperature thermistor
➞
Replace.
Replace outdoor control
PCB.
(Defective underneath
temperature thermistor
input circuit)
2. Error detection method
When anoumalous low
temperature (resistance) is
detected by the underneath
temperature thermistor
3. Condition of Error displayed
If the temperature thermistor
detcts -50°C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after compressor ON,
the compressor stops. When
the compressor is restarted
automatically after 3-minutes
delay, if this anomaly ocuurs 3
times within 40 minute.
4. Presumable cause
• Defective underneath
temperature thermistor
connection
• Defective underneath
temperature thermistor
• Defective outdoor control
PCB
Note: