'11 • PAC-T-160
Error code
Remote controller:
LED
Green
Red
Outdoor
Content
1 time flash
Indoor Keeps flashing
Keeps flashing
Stays OFF
E49
Low pressure error or
low pressure sensor anomaly (2/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
service valve fully
opened?
Are the
connections of low
pressure sensor and suction pipe
temprerature thermister
connector OK?
NO
YES
NO
YES
Are the
characteristics of
low pressure sensor, suction
pipe temperature
thermistor OK?
Is the low
pressure normal during
operation?
Continued from previous page.
Open fully.
Correct.
Defective low pressure
sensor, suction pipe
temperature thermistor
➞
Replace.
Charge refrigerant.
Defective outdoor control
PCB
➞
Replace.
(Defective low pressure
sensor, suction pipe
temperature thermistor
circuits)
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note: