169
-
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
'11 • PAC-T-160
E14
Communication error
between master and slave indoor units
Keeps flashing 3 times flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it
OK the unit
address setting for master
and slave indoor
units?
NO
YES
Isn’t
the remote
controller wiring between
indoor units
defective?
Is it
restored by resetting the
power supply?
Note (1) Set dip switches SW5-1 and SW5-2 as shown in the following table.
(Factory default setting – “Master”)
Master
Slave-a Slave-b Slave-c
SW5-1
OFF
OFF
ON
SW5-2
OFF
ON
OFF
ON
ON
Dip
switch
Indoor unit
YES
NO
NO
YES
Correct unit address setting.
Correct wiring.
Defective indoor control
PCB Replace.
• Malfunction by noise
• Check surrounding
environment.
2. Error detection method
When communication error
between master and slave indoor
units occurs
3. Condition of Error displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote controller wire
• Defective remote controller
wire connection
• Defective indoor control PCB
Note: