Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
–
178
–
'11 • PAC-T-160
E39
Discharge pipe
temperature thermistor anomaly
.HHSVÀDVKLQJ
Stays OFF
.HHSVÀDVKLQJ WLPHÀDVK
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
discharge pipe
temperature thermistor
connector connected
properly?
YES
Are the
characteristics
of discharge pipe
temperature
thermistor
OK?
NO
For the characteristics of discharge pipe
temperature thermistor, see the following graph.
YES
温
度
セ
ン
サ
抵
抗
〔
T?80?
〕
温
度
セ
ン
サ
抵
抗
〔
T?80?
〕
温 度〔T〕
(
?
)
T?80?
T?80?
100
50
0
10
5
0
0
50
80
100
(k)
(k)
0
20
40
60
80
100
120
140
160
180
200
0
20
40
60
80
100
120
140
160
NO
Temperature-resistance characteristics
Temperature thermistor resistance (k
)
Temperature (°C)
(Broken wire)
(Shot circuit)
Correct connector.
Defective discharge pipe
temperature thermistor
ª
Replace.
Defective outdoor control
PCB
ª
Replace.
(Defective temperature
thermistor input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the discharge pipe temperature
thermistor
3. Condition of Error displayed
When the temperature thermistor
detects -10°C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after the compressor
ON, the compressor stops. After
3-minutes delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes.
4. Presumable cause
• Defective outdoor control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note: