136
-
'11 • PAC-T-160
2) Model FDC100VS, 125VS, 140VS
a)
Replace the PCB
after elapsing 3 minutes from power OFF
.
(
Be sure to measure voltage (DC)
on both capacitor terminals located in controller back, and
check that the
voltage is discharged sufficiently
.(Refer to Fig.1))
b)
Take off the connection of inverter PCB terminal block connector and remove the screw of power transistor then
UHPRYHWKH3&%:LSHRIIWKHVLOLFRQJUHDVHQHDWO\RQWKHFRQWUROOHU¶VUDGLDWLRQKHDW¿QV
c)
Refer to table1 for the setting of switch (JSW10,11) of new PCB.
G
%HIRUH LQVWDOOLQJ WKH SRZHU WUDQVLVWRU RQ WKH QHZ 3&%$SSO\ XQLIRUPO\ D EXQGOHG RI VLOLFRQ JUHDVH ¿UVW RQ WKH
surface of power transistor.Make sure it is applied to prevent damage on power transistor.
H
7LJKWHQWKHVFUHZRISRZHUWUDQVLVWRURQLQYHUWHU3&%DQGFRQQHFWWKHWHUPLQDOEORFN&RQ¿UPWKHFRQQHFWLRQDQG
don’t use soldering in the connection.Tighten properly the power transistor with a screw and make sure there is no
clearance gap.Power transistor can be damage if not properly tighten.(Recommended power transistor tightening
torque:0.98~1.47N·m)
Parts No.
Parts arrangement view
Fig.1 Position of capacitor
TB5
TB6
CNI2
Connector
CNR
TB7
TB8
TB9
Voltage measurement parts
Switch
JSW11
JSW10
CNW2
Terminal
block
CNO1
CNW1
-1
OFF -1
OFF
-2
OFF -2
ON
-3
OFF -3
OFF
JSW10
-4
OFF
JSW11
-4
ON
Table. 1 Switch setting
PCA012D025C