(7) Inverter checker for diagnosis of inverter output
䇭䃂
Checking method
ON/OFF
status of L
ED
If all of L
ED are ON/OFF
according to following pattern
If all of L
ED stay OFF or
some of L
ED are ON/OFF
Inverter PCB
Normal
Anomalous
15 sec.
5sec.
5sec.
5sec.
During this period, ON/OFF status of L
ED is
repeated cyclically according to following pattern
(a) Setup procedure of checker.
1) Power OFF (Turn off the breaker).
2) Remove the terminal cover of compressor and disconnect the wires (U
, V, W) from compressor.
3) Connect the wires U
(Red) , V (White) and W (Black) of checker to the terminal of disconnected wires (U
, V, W)
from compressor respectively.
(b) Operation for judgment.
1) Power ON after JSW10-4 on outdoor inverter PCB was turned ON.
2)
After 15 seconds since power has turned ON
L
ED start ON/OFF for 5 seconds cyclically and it repeats 10 times.
3) Check ON/OFF status of 6 L
ED's on the checker.
4) Judge the PCB by ON/OFF status of 6 L
ED's on the checker.
e) Be sure to turn off JSW10-4 on outdoor inverter PCB, after finishing the check operation.
Power ON or start check operation
1
2
3
10
Cyclically
䃂䇭
ON
䂾䇭
OFF
Red
Black
White
Faston terminal
ޛ
Inverter Checker
ޜ
Connect to the terminal of the wires which are disconnected from compressor.
LED ON/OFF pattern
Содержание FDC100VNA
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...