21
-
'11 • PAC-T-160
PGA000Z780
FDF250VSPVD
Indoor unit
FDF125VD (2 units)
Outdoor unit
FDC250VS
Power source
380-415V 3N~50Hz / 380V 3N~60Hz
Operation data
Cooling
Heating
Nominal capacity
kW
25.0 [ 10.0 (Min.)~28.0 (Max.)]
28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption
kW
8.95
9.17
Running current
A
13.2 / 13.9
13.5 / 14.2
Power factor
㧑
98
98
Inrush current
A
5 < Max.running current 22 >
Sound Pressure Level
dB(A)
P-Hi : 54 Hi : 50 Me : 48 Lo : 44
Cooling : 57
ẅ
Heating : 58
Exterior dimensions
Height x Width x Depth
Exterior appearance
Ceramic White
Stucco White
Net weight
kg
52
140
Refrigerant equipment
Model
Item
mm
1,850 × 600 × 320
1,505 × 970 × 370
Compressor type & Q'ty
—
GTC5150ND70K × 1
Starting method
—
Direct line start
Refrigerant oil
—
1.45 M-MA32R
Heat exchanger
Louver fine & inner grooved tubing
Straight fin & inner grooved tubing
Refrigerant control
—
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 1
Propeller fan × 2
Motor <Starting method>
W
157 < Direct line start >
86 × 2 < Direct line start >
Air flow(Standard)
CMM
P-Hi : 29 Hi : 26 Me : 23 Lo : 19
Cooling : 150, Heating : 145
External static pressure
Pa
0
Outside air intake
Not possible
—
—
Air filter, Q'ty
Plastic net × 1 (Washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for Compressor )
Insulation (noise & heat)
Polyurethane form
—
Electric heater
W
—
33 (Crank case heater)
Remote controller
RC-E4 Installed / wireless : RCN-KIT3-E (option)
Room temperature control
Thermostat by electronics
—
Safety equipment
Overload protection for fan motor
Internal thermostat for fan motor
Frost protection thermostat
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
Connecting method
Flare piping
Liquid : Flare
ᵍ
Gas : Brazing
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant
ẅẅ
Quantity
R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump
—
—
Drain
Insulation for piping
Necessary (both Liquid & Gas lines)
Standard Accessories
Mounting kit
Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
ẅ
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(7) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
mm
(Munsell color)
(N8.0) near equivalent
(4.2Y7.5/1.1) near equivalent
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
See page 43
Hose Connectable with VP20
Max.70m
Indoor air temperature
Operation
DB
27
o
C
20
o
C
7
o
C
6
o
C
19
o
C
35
o
C
24
o
C
WB
DB
WB
Cooling
Heating
Item
Outdoor air temperature
(6) Branching pipe set "DIS-WB1" × 1(option).
Ṟ
: Pipe of O/U~Branch,
ṟ
: Pipe of Branch~I/U
Adapted to
RoHS
directive
Holes size
᷑
20 × 3pcs
Gas line: I/U
₥
15.88 (5/8")
ℳ₥
15.88 (5/8") × 1.0
Ⅎ₥
22.22 (7/8") × 1.0 O/U
₥
22.22 (7/8")
Liquid line: I/U
₥
9.52 (3/8")
ℳ₥
9.52 (3/8") × 0.8
Ⅎ₥
12.7 (1/2") × 0.8 O/U
₥
12.7 (1/2")