201
-
'11 • PAC-T-160
Simple Remote Controller Installation Manual
Read together with indoor unit's installation manual.
WARNING
●
Fasten the wiring to the terminal securely and hold the cable securely so as not to apply
unexpected stress on the terminal.
Loose connection or hold will cause abnormal heat generation or fire.
●
Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
CAUTION
●
DO NOT leave the remote controller without the upper case.
In case the upper cace needs to be detached, protect the remote controller with a packaging box
or bag in order to keep it away from water and dust.
●
DO NOT install the remote controller at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight
(4) Hot surface or cold surface enough to generate condensation
(2) Places near heat devices
(5) Places exposed to oil mist or steam directly
(3) High humidity places
(6) Uneven surface
Accessories
Remote controller, wood screw (
Ǿ
3.5
×
16) 2 pieces
Prepare on site
Remote controller cord (2 cores) (Refer to [2. Installation and wiring of remote controller])
[In case of embedding cord] Electrical box, M4 screw (2 pieces)
[In case of exposing cord] Cord clamp (if needed)
1.
Installation procedure
In case of embedding cord
⑴
Make certain to remove the screw on the bottom
surface of the remote controller.
⑵
Remove the upper case of the remote controller.
Insert a flat-blade screwdriver to a concave portion of the bottom
surface of the remote controller and slightly twist it, and the case is
removed.
⑶
Pre-bury the electrical box and remote controller cord.
⑷
Prepare two M4 screws (recommended length: 12 – 16mm), and install the lower case to the electrical box.
Do not use a screw whose screw head is larger than the height of the wall around the screw hole.
⑸
Connect the remote controller cord to the terminal block.
Connect the terminals (X and Y) of the remote controller and the terminals (X and Y) of the indoor
unit. (No polarity of X and Y)
⑹
Mount the upper case for restoring to its former state so as not to crimp the remote controller cord,
and secure with the removed screw.
In case of exposing cord
⑴
Make certain to remove a screw on the bottom surface of the
remote controller.
⑵
Remove the upper case of the remote controller.
Insert a flat-blade screwdriver to a concave portion of
the bottom surface of the remote control and slightly
twist it, and the case is removed.
⑶
The remote controller cord can be extracted from the
upper center.
After the thin part in the upper side of the remote
controller upper case is scraped with a nipper or knife,
remove burr with a file.
⑷
The lower case of the remote controller is mounted to
a flat wall with two accessory wood screws.
⑸
Connect the remote controller cord to the terminal block.
Connect the terminals (X and Y) of the remote controller and
the terminals (X and Y) of the indoor unit. (No polarity of X and
Y)
The wiring route is as shown in the right.
The wiring in the remote controller case should be 0.3 mm
2
(recommended) to 0.5 mm
2
at
maximum.
Further, peel off the sheath.
The peeling length of each wiring is as follows:
X wiring : 160mm
Y wiring : 150mm
⑹
Mount the upper case for restoring to its former state so as not to
crimp the remote controller cord, and secure with the removed screw.
⑺
In the case of exposing installation, secure the remote controller cord to the wall surface with a
cord clamp so as not to loosen the remote controller cord.
2.
Installation and wiring of remote controller
⑴
Wiring of remote controller should use 0.3mm
2
× 2 core wires or cables. (on-site configuration)
⑵
Maximum prolongation of remote controller wiring is 600 m.
If the prolongation is over 100m, change to the size below.
But, the wiring in the remote controller case should be 0.3mm
2
(recommended) to 0.5mm
2
.
Change the wire size outside of the case according to wire connecting. Waterproof treatment is
necessary at the wire
connecting section. Be careful about contact failure.
100 - 200m
・・・・・・・・・・・・・・・・・
0.5mm
2
× 2 cores
Under 300m
・・・・・・・・・・・・・・・・・
0.75mm
2
× 2 cores
Under 400m
・・・・・・・・・・・・・・・・・
1.25mm
2
× 2 cores
Under 600m
・・・・・・・・・・・・・・・・・
2.0mm
2
× 2 cores
PJZ012D069
Screw
⑴
Lower case
Wall
surface
⑷
㪯 㪰
⑸
⑶
Remote controller cord
Electrical box
Prepare on site
Two M4 screws (head: ø8 or less) (prepare on site)
⑷
Screw
⑴
Sheath
Peeling length
Wiring outlet
Lower case
⑵
Upper case
⑵
Upper case
⑶
Thin part
Содержание FDC100VNA
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...