Power supply system error
(Power supply to indoor control PCB)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
NO
NO
Are fuses OK (2 pcs.)?
YES
YES
YES
NO
Is the
check of resistance between
-
of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
NO
Note(1) F200, F201
(1)
(2)
Note (2)
for GND
Is DC5V
detected between
-
of CNW2?
NO
Is
AC380/415V
for 3-phase unit detected
between 1, 2 and 3 on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
1 and 2 on the terminal
block of outdoor
unit?
YES
YES
YES
YES
Is JX1 open?
Defective outdoor control
3&%1RLVH¿OWHU
Misconnection or breakage
of connecting wires
Defective indoor control or
power PCB
ª
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor power
PCB
ª
Replace.
Open JX1.
Defective indoor control
PCB
ª
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note:
Error code
Remote controller:
LED
Green
Red
Indoor Stays OFF Stays OFF
Outdoor Stays OFF 2 times flash
Content