–
196
–
'11 • PAC-T-160
E60
Compressor rotor lock error
(Models FDC200, 250 only)
1. Applicable model
5. Troubleshooting
Models FDC200, 250
Diagnosis
Countermeasure
Is the
power supply voltage
OK?
NO
Reset the power supply and restart operation.
YES
Does the compressor start?
Does E59 occur?
NO
YES
Does it
start up normally without
recurrence of
E60.
YES
NO
Does the
compressor run without
occurrence of
E42?
NO
YES
Is the noise
or vibration of compressor
normal?
Is the
output from inverter
checker OK?
YES
YES
NO
NO
NO
Check and correct the
power supply voltage
Correct it based on the
troubleshooting of E59
Correct it based on the
troubleshooting of E42
Defective inverter PCB
ª
Replace.
replace also the power
transistor module.
Replace compressor.
Check compressor for
insulation, resistance.
Replace compressor if
necessary.
Defective inverter PCB
ª
Replace.
replace also the power
transistor module.
2. Error detection method
Compressor rotor position
3. Condition of Error displayed
If it fails again to detect the
rotor position after shifting to
the compressor rotor position
detection operation, the
compressor stops.
When it is restart
automatically after 3 minutes,
it is detected 4 times within 15
minutes.
4. Presumable cause
• Defective outdoor fan motor
• Defective outdoor control
PCB
• Defective inverter PCB
• Anomalous power supply
voltage
• Improper refrigerant amount
and refrigerant circuit
• Defective compressor (motor,
bearing)
Note: Insulation resistance
• The unit is left for long period without power supply or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M
:
or lower. If the electric leakage breaker is activated due to low insulation resistance, check followings.
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, migrated liquid refrigerant in the refrigerant oil in compressor can be evaporated)
&KHFNZKHWKHUWKHHOHFWULFOHDNDJHEUHDNHFRQIRUPVWRKLJKKHUPRQLFVSHFL¿FDWLRQV
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Error code
Remote controller:
LED
Green
Red
Outdoor
Content
Indoor Keeps flashing
Keeps flashing
Stays OFF
1
7
time flash
Note (1) Value in
are for the Models SRC40 ~ 60.
Содержание FDC100VNA
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...