-
172
-
E20
-
Indoor fan motor
rotation speed anomaly
.HHSVÀDVKLQJ WLPHÀDVK
.HHSVÀDVKLQJ
Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan
propeller?
Is DC280V
detected between
-
of
fan motor connector
CNM?
Does it become normal?
Is the fuse F202 blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
NO
YES
Reset the power supply and restart.
(1)
Note (1)
for GND
Remove foreign material.
Replace the fan motor.
Check power supply
voltage.
Replace fan motor and
power PCB.
Replace fan motor. (If the
anomaly persists after
replacing the fan motor,
replace the indoor control
PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of error displayed
When the actual fan rotation
speed does not reach to the
speed of [required speed
ņUSP@DIWHUPLQXWHVKDYH
been elapsed since the fan
motor rotation speed command
was output, the unit stops by
detecting indoor fan motor
anomaly.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan propeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Error code
Remote controller:
L
ED
G
reen
Red
Indoor
Outdoor
Content
'11 • PAC-T-160
Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
Содержание FDC100VNA
Страница 81: ... 80 80 11 PAC T 160 ...
Страница 82: ... 81 81 11 PAC T 160 ...
Страница 83: ... 82 82 11 PAC T 160 ...