M800/M80/E80 Series Maintenance Manual
4 Failure Diagnosis
131
IB-1501273-F
(3) When the display's IP address is automatically searched, it is searched from among up to 254 IP addresses whose up-
per 3 bytes coincide with those of the local IP address (#1934 Local IP address).
However, depending on the setting of the 4th byte of the PC subnet mask (PC Subnet), the search range may be limited.
(Example 1) General setting
<Setting example>
NC IP address: 10.97.12.16
PC subnet mask: 255.255.255.0
<Search range>
From between 10.97.12.1 and 10.97.12.254, the smallest free address is searched.
(Example 2) When the search range is limited up to 254 addresses
<Setting example>
NC IP address: 10.97.12.16
PC subnet mask: 255.255.0.0
<Search range>
From between 10.97.12.1 to 10.97.12.254, the smallest free address is searched.
(Example 3) When the search range is limited to 254 addresses or less
<Setting example>
NC IP address: 10.97.12.16
PC subnet mask: 255.255.255.128
<Search range>
From between 10.97.12.1 to 10.97.12.126, the smallest free address is searched.
4.13.3 Message
The following messages display when IP address is reset.
Message
Description
Searching
- The system is searching the connectable NC control unit to establish the commu-
nication between the control unit and the display unit. Please wait until the search
is completed.
Socket error
- The system could not find the connectable control unit because of the network
interference.
Turn OFF the NC power supply, and review the wiring for the network connection.
Setting error- Connect NC address
- The automatic connection with the control unit failed because the setting file to
set and save the unit's IP address was not found/is read-only/is of an illegal format.
Review "[HOSTS] TCP1" setting in the setting file "melcfg.ini".
Searching IP address
- The system is automatically searching the appropriate IP address because IP ad-
dress of the display unit is inapposite. Please wait until the search is completed.
Review the setting of the Ethernet
parameter after the screen starts.
- The IP address setting of connected control unit and display unit was completed.
Please review the setting of the Ethernet parameter after the screen starts.
Searching PC IP address failed.
- No empty IP address was found by the automatic search for the IP address of the
display unit.
Please remove the control unit from the network, and turn ON the NC power supply
again.
Содержание E80 Series
Страница 1: ......
Страница 7: ......
Страница 17: ......
Страница 19: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 28: ...1 1 IB 1501273 F System Basic Configuration ...
Страница 68: ...2 41 IB 1501273 F Daily Maintenance and Periodic Maintenance ...
Страница 78: ...3 51 IB 1501273 F Maintenance of the Drive Unit ...
Страница 101: ...M800 M80 E80 Series Maintenance Manual 3 Maintenance of the Drive Unit 74 IB 1501273 F ...
Страница 102: ...4 75 IB 1501273 F Failure Diagnosis ...
Страница 165: ...M800 M80 E80 Series Maintenance Manual 4 Failure Diagnosis 138 IB 1501273 F ...
Страница 166: ...5 139 IB 1501273 F Troubleshooting ...
Страница 169: ...M800 M80 E80 Series Maintenance Manual 5 Troubleshooting 142 IB 1501273 F ...
Страница 170: ...6 143 IB 1501273 F Replacing Each Unit ...
Страница 194: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 167 IB 1501273 F FCU8 DX651 Mounting screw size M5 ...
Страница 205: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 178 IB 1501273 F ...
Страница 212: ......